| |
TECH TIDBITS, vol. 3
Evaluating
bid tenders includes verification that the equipment bid will be
able to complete the drilling program specified, i.e. well depth,
lengths of each casing string, specified mud delivery and conditioning,
etc. However, sometimes the capabilities as identified by manufacturer
and model number may not reflect the operating capacities as installed.
The following are two case studies to illustrate this situation.
| 1.
Mud delivery - Specifications in the inquiry required 1,000
gpm at 4,500 psi. The contractor equipment list showed two mud
pumps which the vendor data sheets show as capable of delivering
approximately 430 gpm at 4,670 psi each. No problem, right?
After
contracting the rig, during acceptance it was discovered these
mud pumps were fitted with 1,000 hp motors. In order to deliver
the nameplate specifications, a 1,600 hp driver is required.
The contractor replaced the installed motors with larger ones
capable of delivering the mud needed for the program. Recognizing
this as part of the acceptance allowed execution of the drilling
program as designed.
|
 |
|
There
are several reasons why this "mismatch" could have
occurred.
| a. |
Some
contractors choose to install lower horsepower electric
motors than the maximum input power rating for a specific
mud pump if the anticipated service conditions will permit
(e.g. high circulation rate, low standpipe pressure),
thus saving the incremental cost of the more powerful
motor. |
| b. |
Another
reason for the lower horsepower drivers could be improved
pump service life (increased engineering factor of safety).
|
| c. |
In
certain cases, equipment availability may be an issue,
and lower powered motors are selected simply to more expeditiously
get back to work. Once installed, they remain in service
until the next replacement cycle.
|
|
|
|
2.
Hoisting and braking - Acceptance of one rig resulted in recognizing
that the eddy current brake recommended by the drawworks manufacturer
was not installed, but one of a lower capacity. Discussions
with both the drawworks and eddy current brake manufacturers
suggested the possibility that the braking capacity was adequate,
but only if the controls were configured and installed to utilize
the drawworks motors as regenerative brakes. The rig could not
confirm the controls configuration.
A
drawworks braking capacity test was designed and conducted,
confirming sufficiency of this capacity as installed.
|
Both
cases illustrate the importance of careful assessment and acceptance
of rig equipment to ensure performance requirements will be achieved.
Procedures that do not require checking the matching of system components
could result in hiring a rig that is not suitable for the program
you have designed.
|