| |
TECH TIDBITS, vol. 2
Potential
Electrical Protective Relay Problems
Every
piece of electrical equipment on every rig is installed with a device
or devices of some type to prevent damage, ranging from the simplest,
fuses, to complex protective relays. These devices are used to isolate
equipment from the problem when conditions exist that can cause
damage, including under and over voltage, current, frequency, load
imbalance and some combinations of the above.
While
conducting generator testing on one rig recently, a generator tripped
off-line on two occasions due to differential current. The load
imbalance in this case was a difference of 1.65 MW between transformer
phases, which would cause a fire. However, both times, no problem
was identified. The drilling contractor contacted the manufacturer,
GE, and learned of potentially defective protective equipment.
 |
WEST
confirmed that differential current tripping problems have
been documented from Multilin SR 489 relays that were loaded
with a particular version of firmware. Only relays with certain
serial numbers are affected. Accordingly, those rigs that
utilize these Multilin SR 489 protective relays should review
the relay serial numbers to understand susceptibility to false
trips from their installed firmware. Two of the six installed
on the referenced rig, including the one responsible for the
false trips, fit the criteria requiring the upgraded firmware.
Please see the GE Multilin Service
Bulletin for more information.
|
return
to top
|